Armenia Acrel ASJ10L-LD1A Residual Current Relays to Monitor Leakage Current Measure Residual Current
Category:
Product Description
Overview
ASJ Series of action relay of after-current, low-voltage circuit break or low-voltage contactor can be made up for combined after-current production device, which is mainly applied for the TT and TN system distributing circuit with the alternating current 50Hz, the rated voltage 400V or below.
ASJ Series of action relay of after-current is applied in the earth fault protection for the electric circuit, so as to prevent the equipment damage and the fire accident of electric equipment caused by the ground fault current, moreover, it also can provide indirect contact protection against the electric shock risk.
The product is qualified in accordance with the requirement of GB/T 22387—2008 Action Relay of After-Current.
Dispaly

Application

Network

Models
|
type |
basic function |
installing way |
picture |
|
ASJ10-LD1C |
Measurement of AC-type after-current; Indicator of current off-limit alarm; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two-pair relay output; Possessing the function of on-the-spot and long-distance testing and resetting
|
rail guiding (TS35mm) |
|
|
ASJ10-LD1A |
The measurement of A-type after-current; The streamer display of current percentage; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two- pair relay output(both of which can be set) *; Possessing the function of on-the-spot and long-distance testing and resetting
|
|
|
|
ASJ10L- LD1Anote 2 |
Type A residual current measurement;
Rated residual action current can be set (see 8.1) ; Limit non-driving time can be set (see 8.1) ; Two sets of relay outputs (settable, see 8.1) ; The fault alarm of transformer can be set (see 8.1) ; Warning value can be set (see 8.1) ; Return value can be set (see 8asj10l-LD1A programming menu description) ; With on-site, remote "test" , "reset" function, 25 event records; |
|
|
|
ASJ20-LD1C |
Measurement of AC-type after-current; Indicator of current off-limit alarm; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two- pair relay output; Possessing the function of on-the-spot and long-distance testing and resetting |
Screen structure (48 square) |
|
|
ASJ20-LD1A |
The measurement of A-type after-current; The streamer display of current percentage; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two- pair relay output(both of which can be set) note 1; Possessing the function of on-the-spot and long-distance testing and resetting
|
|
Note 1:The function of setting for relay means that you can set the initialization and the output of the relay by yourself, which is acted by the dial switch on the panel; the specific setting guide can be found from the table 5.
Note 2:OPTIONAL FUNCTION C: RTU Communication RS485, Model ASJ10L-LD1A/C
Models of Residual Current Transformers
|
type |
bore diameter |
major loop current |
no-load voltage ratio |
|
AKH-0.66L45 |
45mm |
80A |
1A:1mA |
|
AKH-0.66L80 |
80mm |
250A |
1A:1mA |
|
AKH-0.66L100 |
100mm |
400A |
1A:1mA |
|
AKH-0.66L150 |
150mm |
630A |
1A:1mA |
|
AKH-0.66L200 |
200mm |
1000A |
1A:1mA |
|
AKH-0.66L-260*100II |
265*104mm |
1000A |
1A:1mA |
Technical Parameters
|
technical parameter |
index |
|||
|
Type AC |
Type A |
|||
|
input |
Rated residual action current I△n |
0.03、0.1、0.3、0.5(A) |
0.03、0.05、0.1、0.3、0.5、1、3、5、10、30(A) note 3 |
|
|
Non-driving time of limitation △t |
0.1、0.5(s) |
0、0.06、0.1、0.2、0.3、0.5、0.8、1、4、10(s) note 4 |
||
|
Rated residual non-action current I△no |
50%I△n |
50%I△n |
||
|
performance characteristics |
simple sinusoidal alternating current |
simple sinusoidal alternating current and pulsating direct current |
||
|
frequency |
50Hz±5Hz |
50Hz±5Hz |
||
|
action error |
-20% ~ -10%I△n |
-20% ~ -10%I△n |
||
|
output |
output mode |
one is the normal closing and the other is for the transformation |
one is the normal closing or opening, and the other is for the transformation |
|
|
contact capacity |
5A 250VAC 5A 30VDC |
AL1:8A 250VAC 5A 30VDC AL2:6A 250VAC 5A 30VDC |
||
|
reset mode |
the on-the-spot one and the long-distance one, |
the on-the-spot one, the long-distance one and the automatic one |
||
|
power supply |
voltage range |
AC110V、AC220V(permissible error±10%) |
AC110V、AC220V、DC85-270V (permissible error±10%) |
|
|
power dissipation |
≤5W |
|||
|
power frequency withstand voltage |
The effective value of alternating current between the power supply, input and output: 2kV/1min
|
|||
|
under the normal operation |
temperature |
operating temperature: -20℃ ~ +55℃ storage temperature: -30℃ ~ +70℃
|
||
|
humidity |
≤95%RH, with moisture condensation, and corrosive gas place |
|||
|
height above sea level |
≤2000m |
|||
|
class of pollution |
Grade three |
|||
|
installation category |
Type Ⅲ |
|||
Note 3:ASJ10L-LD1A rated residual action current I N is 10mA-30A continuously adjustable;
Note 4:ASJ10L-LD1A limit non-driving Time N is 0-10S continuously adjustable.
Wiring

Dimension