PRODUCTS CENTER
Bahrain Acrel AIM-T500L Industrial Insulation monitoring instrument
Product Description
Overview
With the development of industrial science and technology, residual current poses a great threat to industrial production safety. In order to improve the continuity and reliability of power supply, many important production sites adopt IT distribution system (ungrounded system).
AIM-T500L series industrial insulation monitoring and fault is specially developed by Acrel for IT distribution system in industrial occasions such as mine, glass factory, electric furnace and test equipment, ship, metallurgical plant, chemical plant, explosion hazard site, computer center and emergency power supply.
The system has rich functions, including insulation resistance monitoring, insulation fault warning, insulation fault alarm, event recording, parameter setting, communication networking, etc. When the system has grounding fault, it can give a timely alarm and accurately locate the specific circuit of the fault to remind staff to check the fault in time.
The products conform to the requirements of enterprise standard Q/VDCL-26-2017 IT System Insulation Monitor.
Dispaly

Application


Features
1. AIM-T500L insulation monitor
■ Monitor resistance of IT system real time, warning or alarm when the resistance exceeds the limit;
■ Relay alarm output, LED alarm output and other fault indication modes;
■ SOE function, convenient for staff to check and analyze the failure type and occurrence time, and judge the operation status of the system;
■ Self-check function, which can realize fault self-check of instrument hardware circuit;
■ Disconnect monitoring, real-time monitoring of PE/KE function grounding wire connection status;
■ RS485 interface, standard Modbus-RTU protocol;
■ CAN interface, custom protocol, used to interact with signal generator and fault locator;
■ Support manual/automatic reset modes;
■ Wide range of applications, suitable for AC, DC and AC-DC hybrid IT systems.
2. ASG200 test signal generator
■ Generate positioning signals and inject them into the ungrounded system;
■ Indicate the phase line where the fault is;
■ Manual startup positioning is supported;
■ CAN bus technology is adopted to facilitate data interaction with other devices in the system.
3. AIL200-12 insulation fault locator
■ Locate and indicate the loop where the fault is;
■ A single AIL200-12 can locate up to 12 loops;
■ Each IT system can be connected to a maximum of 90 locators, with a total of 1080 loops;
■ CAN bus technology is adopted to facilitate data interaction with other devices in the system.
4. AKH-0.66L series current transformer
■ Rated current ratio 5A:5mA , select model according to the rated current of the loop;
■ Coordinate with AIL200-12 insulation fault locator to achieve fault location.
Network


Technical Parameters
1. AIM-T500L insulation monitor
|
Item |
Parameter |
|
|
Accessory power supply |
AC 85~265V; DC100~300V; 50/60Hz |
|
|
Power dissipation |
< 8W |
|
|
System voltage |
AC 0~690V; DC 0~800V; 40~460Hz |
|
|
System application |
IT system (online), Other system (offline) |
|
|
Insulation monitoring |
Measuring range |
1k~10MΩ |
|
Alarm range |
10k~10MΩ |
|
|
Resistance accuracy |
1~10k,1k; 10k~10M, ±10% |
|
|
system leakage capacitance |
<500μF |
|
|
Response time (Ce=1μF) |
<5s |
|
|
Internal parameters |
Measuring voltage |
<50V |
|
Measuring current |
<270μA |
|
|
Internal DC impedance |
≥180kΩ |
|
|
Relay output |
Error, Alarm, Warning |
|
|
SOE |
20 records (fault type, fault value, fault time) |
|
|
Alarm type |
LCD, LED indicator |
|
|
Communication |
RS485, Modbus-RTU; CAN, custom |
|
|
Impulse voltage / Pollution Level |
8kV/Ⅲ |
|
|
EMC/ Radiation |
IEC61326-2-4 |
|
|
Environment |
Working temperature |
-10 ~+65℃ |
|
Storage temperature |
-20~+70℃ |
|
|
Relative humidity |
<95%, without condensation |
|
|
Altitude |
≤2500m |
|
2. ASG200 test signal generator
|
Accessory power supply |
Voltage |
AC 85~265V; DC100~300V |
|
Power dissipation |
<7W |
|
|
IT system |
Voltage |
AC 220V; 3AC 0~690V; DC 0~800V |
|
Fault locating |
Response time |
<5s |
|
positing voltage |
20V/5Hz |
|
|
positing current |
0~10mA |
|
|
Response sensitivity |
—— |
|
|
Internal parameters |
EMC/ Radiation |
IEC61326-2-4 |
|
Output |
Relay output |
—— |
|
Environment |
Working temperature |
-15~+55℃ |
3. AIL200-12 insulation fault locator
|
Accessory power supply |
Voltage |
AC 85~265V; DC100~300V |
|
Power dissipation |
<5W |
|
|
IT system |
Voltage |
—— |
|
Fault locating |
Response time |
<12s |
|
positing voltage |
—— |
|
|
positing current |
—— |
|
|
Response sensitivity |
>0.5mA |
|
|
Internal parameters |
EMC/ Radiation |
IEC61326-2-4 |
|
Output |
Relay output |
Alarm |
|
Environment |
Working temperature |
-15~+55℃ |
4. AKH-0.66L series current transformer
|
Specifications |
Rated current |
Ratio |
Accurate level |
Rated load |
Overload ratio |
|
L-45 |
16-100A |
5A:5mA |
1 level |
100Ω |
10 |
|
L-80 |
100-250A |
||||
|
L-100 |
250-400A |
||||
|
L-150 |
400-800A |
||||
|
L-200 |
800-1500A |
Related Products
|
Type and Name |
Picture |
Introduction |
|
AIM-T500L insulation monitor |
|
AIM-T500L insulation monitor adopts advanced microcontroller technology, high integration, small size, easy to install, intelligent, digital, networking in one. wide measuring range, fast reaction speed and large allowable system leakage capacitance. |
|
ASG200 test signal generator |
|
ASG200 test signal generator can start and produce test signals in time when insulation fault occurs in the monitored IT system. It can coordinate with insulation fault locator to realize insulation fault location function and send fault phase line. |
|
AIL200-12 insulation fault locator |
|
AIL200-12 insulation fault locator adopts high-precision signal detection circuit, and AKH-0.66L series current transformer, detection the signal of ASG200 test signal generator, accurate location of the insulation fault loop. every locator can locate 12 loops. |
|
AKH-0.66 L series current transformer |
|
AKH-0.66 L series current transformer is used with AIL200-12 insulation fault locator together, ratio is 1000:1. It is installed in the cabinet in the way of screw direct fixation. |
Wiring

Dimension
Installation