PRODUCTS CENTER


Bahrain Acrel ADW600 CE IEC Approved Wireless 4G Digital 3 Phase Multi-channel Energy Meter For IOT Platform Energy Consumption Monitoring

● Measures active kWh (positive and negative), Reactive kWh (positive and negative), U, I, P, Q, S, PF, F, etc. ● Communication: 4G, WiFi, Ethernet, RS485(Modbus-RTU) ● Full electric parameter measurement,Multi Channels independent metering ● With Different Size of CTs,easy to install D10,D16,D24,D36 ● Optional 4DI/2DO,12 channels temp measure,4 channels Residual current monitoring ● Application: for the Multi channels places ● Standard&Certificate: CE; IEC

Product Description

 

 

 

 

Overview

     

 

        The ADW600 multi-circuit power metering module is mainly used to measure three-phase active energy in low-voltage networks, and has the advantages of small size, easy installation, and rich functions.

 

      The product adopts a modular design, including voltage module, current module, switch module, temperature measurement and leakage module, etc.

 

      The modules are connected by Ethernet cables and can support multi circuit splicing. Suitable for low-voltage side multi circuit metering scenarios, especially for power transformation needs.

 

 

 

 

Coding Rule

 

 

 

ADW600 main module

 

 

ADW600 slave module

 

 

 

 

 

Dispaly

 

 

 

 

 

 

Models & Function

 

 

 

model

Functional Description

ADW600-U

Voltage measurement and sampling

ADW600-I

Active energy measurement (forward and reverse),

Four-quadrant reactive energy

Voltage, current, power factor, frequency, active power, reactive power, apparent power

Total harmonic content, sub-harmonic content (2nd to 31st)

Active pulse output

ADW600-K

4DI, 2DO

ADW600-TL

4 channels for temperature measurement, 1 channel for residual current measurement

 
 

 

 

 

       

Network

 

 

 

 

 

 

 

Dimension

 

 

 

1. The ADW600-M gateway (-4G/-CE/-WF) on the far left of the ADW600 rendering in Figure 1 needs to be ordered separately.

2. When connecting network cables between different modules, please note that BUS-IN is the incoming interface and BUS-OUT is the outgoing interface. Start with ADW600-M or th power module and connect them in sequence. Do not connect them in reverse.

 

 

Model

Dimension(mm)

Hole size(mm)

Tolerance(mm)

W

H

D

M

N

Φ1

Φ2

D10:AKH-0.66/K-∅10N

27

44

32

25

36

10

9

±1

D16:AKH-0.66/K-∅16N

31

50

36

27

42

16

17

D24:AKH-0.66/K-∅24N

39

71

46

36

52

24

23.5

D36:AKH-0.66/K-∅36N

42.5

82

58

40

56

33.5

35

 

 

 

 

 

 

 

Wiring

 

 

 

      ADW600 multi-circuit metering modules are connected by network cables. BUS-IN is the incoming interface and BUS-OUT is the outgoing interface. They are connected starting from ADW600-M or the power module and cannot be connected in reverse.

 

      ADW600 -U needs to be connected to the load voltage signal. Refer to the wiring diagram below. Terminals 11-14 are connected to the UA, UB, UC, and UN voltage signals respectively. If the three-phase three-wire connection method is used, terminals 11-13 are connected to the UA, UB, and UC voltage signals, and then UB is short-circuited into the UN terminal.

 

 

 

        ADW600 -I needs to be connected to the load current signal. Refer to the wiring diagram below. The standard transformer is an RJ12 interface that can be inserted into the meter terminal. The three transformers can be clipped onto the load cables according to the indicated directions.

 

 

 

 

      ADW600 -K is connected to the switch input or output signal line as needed. Note that the COM port is the common end. Refer to the wiring diagram below.

 

 

 

 

 

    ADW600 -TL is connected to the temperature measurement signal line or the residual current transformer signal line as needed. Note that the COM port is the common end of the adjacent measurement circuits. The specific wiring diagram is as follows.