PRODUCTS CENTER
Laos Acrel DTSD1352-4S Digital Multi Circuits AC Energy Meter For Tower Base Station Energy Consumption Monitoring
Category:
Product Description
Overview
DTSD1352-4S series DIN-rail type multi-circuit power meter is mainly used for the full electric parameter measurement of multiple circuits, and can be connected to the current input of 4 three-phase circuits or 12 single-phase circuits at the same time.
It can measure parameters such as voltage and current, power, power factor, phase angle, unbalance, and harmonics.
Dispaly

Application

Installation in Tower Base Station
Network


Function
The specific functions are as follows:
①4-way three-phase or 12-way single-phase loop full electric parameter measurement, external current transformer;
②Monitoring each phase voltage/current, zero sequence current, frequency;
③Monitoring each phase power and total power (active, reactive, apparent);
④Monitoring each phase power factor and total power factor;
⑤Monitoring voltage/current phase angle, voltage/current unbalance;
⑥Monitoring total voltage/current harmonics and 2nd to 31th harmonics;
⑦Recording voltage, current and power extreme value of the current month and the previous month;
⑧Maximum current, maximum power demand and real-time current, real-time power demand;200 event loggings to record the actions of DIDO;
⑨Supporting overvoltage, overcurrent, phase failure, DI linkage and other alarm output;
⑩Rate setting for 4 time zones and 14 time periods;Four-quadrant energy, 12-month multi-rate energy statistics;
⑪31-day four-quadrant and multi-rate energy freeze, forward and reverse energy metering;
⑫Four passive switch inputs, two active switch inputs, one switch output, RS485 communication;
⑬Two-way passive switch input, two-way switch output, RS485 communication;
Note: It can only choose either-or between four passive switch inputs, two active switch inputs, one switch output and two passive switch inputs, two switch outputs.
Technical Parameters
| Auxiliary power | AC/DC 85~265V; Consumption≤10VA; | |
|
Input
|
Frequency | 45~65Hz; |
|
Voltage |
AC 3×220V/380V; Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s; Power consumption: ≤ 0.5VA;each channel) |
|
|
Current |
Rated value: Secondary input rated current:50mA;Overload: 1.2 times rated value (continuous); 10 times rated value/1 second;power consumption: ≤ 0.5VA(each channel); |
|
|
Measurement accuracy |
Frequency: 0.05Hz, voltage and current: 0.5 class, active energy: 1 class, reactive energy: 2 class; 2nd to 31st harmonic accuracy: ±1%; |
|
|
Features |
Pulse output | Output method: optocoupler pulse with open collector,the pulse constant defaults to 400imp/kWh (and active open input can only be either-or.); |
| Communication | RS485 interface, Modbus-RTU protocol; baud rate 1200~38400; | |
| Switching Input | 2-way or 4-way passive dry contact input, built-in power supply; 2-way active wet node input (AC220V), identify the oil generator and mainsaccess (and pulse output can only be either-or.); |
|
| Switching Output |
Output method: relay normally open contact output; |
|
| Type | Ratio | Line Length | Accuracy | Installation Method |
| AKH-0.66/W-9NY 50A/20mA | 50A/20mA | (1+0.2)m | Class 0.2 | Closed type, crystal head interface |
| AKH-0.66/K-Φ10N 50A/20mA | 50A/20mA | (1+0.2)m | Class 0.5 | Open type, crystal head interface |
| AKH-0.66/W-12NY 100A/50mA | 100A/50mA | (1+0.2)m | Class 0.2 | Closed type, crystal head interface |
| AKH-0.66/K-Φ16N 100A/50mA | 100A/50mA | (1+0.2)m | Class 0.5 | Open type, crystal head interface |
| AKH-0.66/W-20Y 200A/50mA | 200A/50mA | (1+0.5)m | Class 0.2 | Closed type, crystal head interface |
| AKH-0.66/K-Φ24N 200A/50mA | 200A/50mA | (1+0.5)m | Class 0.5 | Open type, crystal head interface |
| AKH-0.66/W-30NY 250A/50mA | 250A/50mA | (1+0.5)m | Class 0.2 | Closed type, crystal head interface |
| AKH-0.66/K-Φ24N 250A/50mA | 250A/50mA | (1+0.5)m | Class 0.5 | Open type, crystal head interface |
| AKH-0.66-TD-Φ60-NY | 300-1000A/50mA | (1+0.5)m | Class 0.2 | Closed type, crystal head interface |
| AKH-0.66/K-Φ36N 400A/50mA | 400A/50mA | (1+0.5)m | Class 0.5 | Open type, crystal head interface |
| AKH-0.66/K-Φ36N 600A/50mA | 600A/50mA | (1+0.5)m | Class 0.5 | Open type, crystal head interface |
Dimension