Moldova Acrel APM510/4G CE Approved Digital 3 Phase 4G Energy Meter For IOT Platform Energy Consumption Monitoring

● 3 phase 3 wires, 3 phase 4 wires ● Rated voltage: AC 3*57.7/100V, AC 3*63.5/110V, AC 3*230/400V, AC 3*400/690V (96 Shape only); ● Rated current: 1A, 5A ● Accuracy: IEC 62053-22 0.5S class (0.2S accuracy when S is selected) ● Communication: RS485(Modbus-RTU)、Ethernet (MODBUS-TCP)、WiFi、4G ● 2DI+2DO ● kWh  (positive and negative)、kVarh (positive and negative) ● U, I, P, Q, S, PF, Hz, etc. ● A, B, C phase positive active kWh ● Four-quadrant energy、Split phase electricity、Apparent energy、Multi-rate energy ● 2~63ST Voltage and current harmonic(optional) ● Multi tariff: Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates(optional) ● Max demanded kWh and time happened(optional)

Product Description

 

 

Overview

     

 

 

        APM5 series network power meter (hereinafter referred to as the meter) is designed according to IEC international standards, with full power measurement, power statistics, power quality analysis (including harmonics, interharmonics, flicker), fault recording function (including voltage temporary rise and fall interrupt, inrush current and other records), event recording function and network communication and other functions.

 

      It is mainly used for comprehensive monitoring of power supply quality in the power grid.

 

        This series of meters is equipped with feature-rich DI/DO modules, AO modules, wireless communication modules, leakage temperature measurement modules, which can flexibly realize the full electrical circuit Power measurement and switching status monitoring. 

 

 

 

 

 

 

Dispaly

 

 

 

 

 

 

 

Code Rule

 

 

 

 

 

 

Note:1、When the meter is connected by 5A/1.25mA as the two-time mutual inductance method, the meter's own secondary-side transformer should be kept at a distance from the on-site primary-side transformer to avoid out-of-line interference.

 

 

 

 

 

 

Function

 

 

 

 

● 3 phase 3 wires, 3 phase 4 wires

● Rated voltage: AC 3*57.7/100V, AC 3*63.5/110V, AC 3*230/400V, AC 3*400/690V (96 Shape only);

● Rated current: 1A, 5A

● Accuracy: IEC 62053-22 0.5S class (0.2S accuracy when S is selected)

● Communication: RS485(Modbus-RTU)、Ethernet (MODBUS-TCP)、WiFi、4G

● 2DI+2DO

Electricity Data Measurement

● kWh  (positive and negative)

● kVarh (positive and negative)

● U, I, P, Q, S, PF, Hz, etc.

● A, B, C phase positive active kWh

● Four-quadrant energy、Split phase electricity、Apparent energy、Multi-rate energy

● 2~63ST Voltage and current harmonic(optional)

● Multi tariff: Adapt 4 time zones, 2 time interval lists,

14 time interval by day and 4 tariff rates(optional)

● Max demanded kWh and time happened(optional)

● Total active 、Total reactive energy pulse output (72 type only has active energy pulses)

● Three-phase current, active power, reactive power, real-time demand of apparent power, and maximum demand (including time stamp)

● Extreme value statistics: Current, line voltage, phase voltage, active power, reactive power and other electrical parameters extreme values of this month and last month (including time stamps)

● Frozen data on last 48 months, last 90 days(optional)

● Energy pulse output: 1 active photocoupler output

● Key programming: 4 keys to communication and set parameters 

● Starting current: Direct connect: 0.004Ib

 

● Display: 8 digits display U, I, P, Q, PF, kWh and other energy consumption

● Power quality: Unbalance of current, line voltage, phase voltage, Voltage phase angle, current phase angle, Total (odd, even) harmonic content of voltage and current, Harmonic content of voltage and current (2-63 times), Interharmonic (included with option S), Flicker (included with S option), Voltage peak coefficient, Telephone waveform factor, Current K-factor, Vector, Voltage and current waveform, Fundamental voltage and current.

● Record of voltage ramp-up and drop interruptions, inrush currents, etc. (included with S option).

● Mounted: DIDO records, which can record the last 128 DID records 

● The last 128 alarm records can be recorded

● 72 Shape: 2 channels of switching input + 2 channels of switching output;   96 Shape: 4 switching inputs + 2 switching outputs

 

 

 

 

 

       

Network

 

 

 

 

 

 

 

 

 

 

Type & Function

 

 

 

 

 

Measured

parameters

Total electrical measurement

Four-quadrant energy、Split phase electricity、Apparent energy、Multi-rate energy

Pulse output of  energy

Total active 、Total reactive energy pulse output (72 type only has active energy pulses)

Demand

Three-phase current, active power, reactive power, real-time demand of apparent power, and maximum demand (including time stamp)

Extreme

value statistics

Current, line voltage, phase voltage, active power, reactive power and other electrical parameters extreme values of this month and last month (including time stamps)

Power quality

Unbalance of current, line voltage, phase voltage

Voltage phase angle, current phase angle

Total (odd, even) harmonic content of voltage and current

Harmonic content of voltage and current (2-63 times)

Interharmonic (included with option S).

Flicker (included with S option).

Voltage peak coefficient

Telephone waveform factor

Current K-factor

Vector

Voltage and current waveform

Fundamental voltage and current

Fault waveform recording

Record of voltage ramp-up and drop interruptions, inrush currents, etc. (included with S option).

Event logging

DIDO records, which can record the last 128 DID records

Alarm logging

The last 128 alarm records can be recorded

Communication

Modbus - RTU protocol, DL/T 645-2007 statute

Switching value

72 Shape: 2 channels of switching input + 2 channels of switching output;

96 Shape: 4 switching inputs + 2 switching outputs

 

 

 

 

Base model

Basic function

Optional function

Option Group

APM510

2DI2DO1EP1C

1. CE (Ethernet Communication/MODBUS-TCP).

1+5+6+7+8

2+3+4+7+8

5+6+7+8+9

5+6+7+8+10

5+6+7+8+11

5+6+7+8+12

2.2C (Extended 2nd Communication).

3.K (2 switch inputs + 2 switch outputs).

4.2M (2ch analog).

5.T (4-channel NTC temperature measurement).

6.L (1 channel leakage).

7.F (Compound Rate).

8.S (0.2S level + fault recording).

9.WF(WiFi Communication)

10.LR(Lora Communication)

11.4G(4G Communication)

12.NB(NB Communication)

 

 

 

 

Base model

Basic function

Optional function

Option Group

APM520

4DI2DO2EP1C

1. CE (Ethernet Communication/MODBUS-TCP).

1+5+6+7+8

2+3+4+7+8

1+5+6+7+8

2+3+4+7+8

5+6+7+8+9

5+6+7+8+10

5+6+7+8+11

5+6+7+8+12

2.2C (Extended 2nd Communication).

3.K (4-way switching input + 2-way switching output).

4.2M (2ch analog).

5.T (4-channel NTC temperature measurement).

6.L (1 channel leakage).

7.F (Compound Rate).

8.S (0.2S level + fault recording).

9.WF(WiFi Communication)

10.LR(Lora Communication)

11.4G(4G Communication)

12.NB(NB Communication)

 

 

Note: Optional K function, defined as extending the DID on the basis of the basic function; 

 

 

 

 

 

 

Technical Parameters

 

 

 

 

Display

Display method

Dot matrix liquid crystal;  Switch between Chinese and English

Resolution

128*128;

Backlight

White LED;

Visible area

72 Shape: 38mm*46mm (1.78"/2.3");

96 Shape: 56mm*60mm (2.46"/3.2");

Signal

Electrical network

Three-phase three-wire, three-phase four-wire, see the wiring diagram;

Frequency

45~65Hz;

Voltage

Rating: AC 3*57.7/100V, AC 3*63.5/110V, AC 3*230/400V, AC 3*400/690V (96 Shape only);

Overload: 1.2 times the rating (continuous); 2x rating/1 second;

Power consumption: < 0.5VA(Every way);

Current

Ratings: AC 3x 1 (1.2) A, AC 3x5(6)A;

Overload: 1.2 times the rating (continuous); 10x rating/1 second;

Power consumption: < 0.5VA(Every way);

Measurement accuracy

Voltage, current

IEC 61557-12   0.2%

Voltage harmonics, current harmonics

IEC 61557-12   1%

Frequency

IEC 61557-12   ±0.02Hz 

Active power

IEC 61557-12   0.5%

Reactive power

IEC 61557-12   1% 

Active electrical energy

IEC 62053-22 0.5S class (0.2S accuracy when S is selected).

Reactive power

IEC 62053-24  Class 1

Power quality (only available when S is selected).

Waves recording

20 waveforms, 10 waves before and after;

Waveform capture

128 cycle points are stored per waveform;

Switch input

Dry contact input, built-in power supply;

Response time: less than 300ms

Relay output

Contact type: normally open contact;

Contact capacity: AC 250V/3A DC 30V/3A;

Energy pulse output

Output mode: photocoupler pulse with open collector;

Pulse constant: 10000imp/kWh (default);

communication

RS485 interface/Modbus-RTU protocol and DLT645 protocol;

RJ45 interface (Ethernet)/Modbus-TCP protocol;

Wireless interface

power supply

Working range: AC 85V~265V;  DC100V~350V

Power consumption: power consumption≤15VA;

Safety 

Power frequency withstand voltage

The power frequency withstand voltage between the housing and the auxiliary power supply, each input and output terminal group is AC 4kV/1min;

The power frequency withstand voltage between the auxiliary power supply and each input terminal and each output terminal group is AC 2kV/1min;

The power frequency withstand voltage between the voltage input and other input and output terminal blocks is AC 2kV/1min;

The power frequency withstand voltage between the current input and other input and output terminal blocks is AC 2kV/1min;

The power frequency withstand voltage between the relay output and other input and output terminal blocks is AC 2kV/1min;

The power frequency withstand voltage between the terminal groups of switching input, communication, analog output and pulse output is AC 1kV/1min;

Insulation resistance

Inputs、outputs to the shell>100MΩ;

Electromagnetic compatibility

Complies with IEC 61000 standard (Level 4);

Environment

Operating temperature:-25℃~+70℃;Storage temperature:-40℃~+85℃;

Relative humidity:≤95% without condensation;Altitude:≤2500m;

Protection Level

Display panel IP54; (Optionally IP65).

Standards

IEC 60068-2-1

IEC 60068-2-2

IEC 60068-2-30

Environmental Testing-Part 2-1:Tests Test A:Cold IDA

Environmental Testing Part 2-2:Tests Test B:Dry heat

Environmental Testing Part 2-30:Tests Test Db:Damp heat,cyclic (12+12h)

IEC 61000-4

Electromagnetic compatibility-Testing and measurement techniques

IEC 61557-12

Electrical safety in low voltage distribution systems up to 1 000V a.c. and 1 500V d.c –Equipment for testing, measuring or monitoring of protective measures — Part12:Performances measuring and monitoring devices(PMD)

IEC 62053-22

Electricity metering equipment (a.c.)-Particular requirements - Part22:Static meter for active energy(class 0.2S and 0.5S)

IEC 62053-24

Electricity metering equipment (a.c.)-Particular requirements - Part24:Static meter for reactive energy at fundamental frequency (classes 0.5S 1S and 1)

 

 

 

 

 

 

Dimension

 

 

 

 

Outline

 faceplate size

housing size

cutout size

width

 height

width

height

 depth

width

 height

72 square shape

75

75

66.5

66.5

82.8

67

67

96 square shape

96

96

86.5

86.5

77.8

88

88

 

 

 

 

 

APM510 dimensional drawing

 

 

 

 

 

 

APM520 dimensional drawing

 

 

Note: If the instrument is installed side by side on the unified horizontal plane, it is recommended that the instrument opening spacing is 30mm.

 

 

 

 

 

 

Wiring

 

 

 

 

 

 

 

 

 

Installation

 

 

 

 

 

 

 

 

FAQ

 

 

 

Q: Do your company also have paired CTs for APM meters?

A: Usually, we will recommend our user to use split-core CTs called AKH-0.66/K K-φ Series or solid-core CTs called AKH-0.66/I Series to the paired with AMC meters (current input via CTs)

 

 

 

Q: How can I set the CT or PT ratio of APM meters?

A: Current ratio of APM meters could be set by using the keypads on APM meters and following the instruction of APM meters manual. Also, setting need to be according to the CTs or PTs ratio which were paired with APM meters. For example, if the current input is via 250A/5A CTs, the CT ratio on APM meters should be set to 250/5=50. And if the voltage input is via direct connect, PT ratio on APM meters should be set to 1. When the problem hasn’t been solved, please contact us for help.

 

 

 

Q: Could APM series of meters be used in IoT Energy Monitoring System for factory or building?

A: Yes, APM series of meters have standard RS485 interface and MODBUS-RTU communication protocol which allow it to be integrate with our IoT Energy Monitor Solution that can enable our users to remotely check all the data collect by energy meters like APM meters on their mobile phone or PC. For more information, please Contact us or check in IoT Energy Monitoring Solution Introduction.

 

 

 

Q: What is Multi-rate/tariff function? How does it work?

A: First,multi-rate/tariff function was designed to be used for billing system. Second, the electricity price of different time duration in a day is different in some country.

 

Energy meter with this function can measure the kwh data and assign them to several time duration in a day and put a label of spike/peak/flat/valley kwh on them respectively. And if such energy meter was connected to the billing system by using a IoT gateway, it can send the kwh data of different time duration which was with the label of spike/peak/flat/valley kwh to the billing system for calculating the electricity bill of different time duration in a day.

 

For example, the electricity price of spike kwh is 5 USD/1 kwh, and time duration of from 9:00 am to 11:30 am was labeled as spike kwh.


Then, if energy meter record 3 kwh used in total during 9:00 am to 11:30 am, it will send the data of 3 kwh with the label of spike kwh to the billing system, and the system calculate the electricity cost of 3x5=15USD in total from 9:00 am to 11:30 am.

 

 

Other Question? Please contact us and we will get back to you as soon as possible.