PRODUCTS CENTER


Qatar Acrel ASJ60-LD16A Residual Current Relays to Monitor Leakage Current Measure Residual Current

● The measurement of A-type after-current; ● The streamer display of current percentage; ● The setting of rated residual action current ( see in the table 2); ● The setting of non-driving time of limitation ( see in the table 2); ● Two- pair relay output(both of which can be set) *; ● Possessing the function of on-the-spot and long-distance testing and resetting

Product Description

 

 

 

Overview

     

   

      ASJ Series of action relay of after-current, low-voltage circuit break or low-voltage contactor can be made up for combined after-current production device, which is mainly applied for the TT and TN system distributing circuit with the alternating current 50Hz, the rated voltage 400V or below.

 

        ASJ Series of action relay of after-current is applied in the earth fault protection for the electric circuit, so as to prevent the equipment damage and the fire accident of electric equipment caused by the ground fault current, moreover, it also can provide indirect contact protection against the electric shock risk.

 

    The product is qualified in accordance with the requirement of GB/T 22387—2008 Action Relay of After-Current.

 

 

 

 

 

 

Dispaly

 

 

 

 

 

 

 

Application

 

 

 

 

 

 

 

 

 

 

 

 

 

Network

 

 

 

 

 

 

 

 

 

 

 

Models

 

 

 

 

type

basic function

installing way

picture

ASJ10-LD1C

Measurement of AC-type after-current;

Indicator of current off-limit alarm;

The setting of rated residual action current ( see in the table 2);

The setting of non-driving time of limitation ( see in the table 2);

Two-pair relay output;

Possessing the function of on-the-spot and long-distance testing and resetting

 

 

rail guiding

(TS35mm)

 ASJ10-LD1A

The measurement of A-type after-current;

The streamer display of current percentage;

The setting of rated residual action current ( see in the table 2);

The setting of non-driving time of limitation ( see in the table 2);

Two- pair relay output(both of which can be set) *;

Possessing the function of on-the-spot and long-distance testing and resetting

 

 

ASJ10L- LD1Anote 2

Type A residual current measurement;

 

Rated residual action current can be set (see 8.1) ;

Limit non-driving time can be set (see 8.1) ;

Two sets of relay outputs (settable, see 8.1) ;

The fault alarm of transformer can be set (see 8.1) ;

Warning value can be set (see 8.1) ;

Return value can be set (see 8asj10l-LD1A programming menu description) ;

With on-site, remote "test" , "reset" function, 25 event records;

 

ASJ20-LD1C

Measurement of AC-type after-current;

Indicator of current off-limit alarm;

The setting of rated residual action current ( see in the table 2);

The setting of non-driving time of limitation ( see in the table 2);

Two- pair relay output;

Possessing the function of on-the-spot and long-distance testing and resetting

Screen structure

(48 square)

 

ASJ20-LD1A

The measurement of A-type after-current;

The streamer display of current percentage;

The setting of rated residual action current ( see in the table 2);

The setting of non-driving time of limitation ( see in the table 2);

Two- pair relay output(both of which can be set) note 1;

Possessing the function of on-the-spot and long-distance testing and resetting

 

 

 

Note 1:The function of setting for relay means that you can set the initialization and the output of the relay by yourself, which is acted by the dial switch on the panel; the specific setting guide can be found from the table 5.

 

Note 2:OPTIONAL FUNCTION C: RTU Communication RS485, Model ASJ10L-LD1A/C

 

 

 

 

Models of Residual Current Transformers

 

 

type

bore diameter

major loop current

no-load voltage ratio

AKH-0.66L45

45mm

80A

1A:1mA

AKH-0.66L80

80mm

250A

1A:1mA

AKH-0.66L100

100mm

400A

1A:1mA

AKH-0.66L150

150mm

630A

1A:1mA

AKH-0.66L200

200mm

1000A

1A:1mA

AKH-0.66L-260*100II

265*104mm

1000A

1A:1mA

 

 

 

 

 

 

 

Technical Parameters

 

 

 

 

technical parameter

index

Type AC

Type A

input

Rated residual action current I△n

0.03、0.1、0.3、0.5(A)

0.03、0.05、0.1、0.3、0.5、1、3、5、10、30(A) note 3

Non-driving time of limitation △t

0.1、0.5(s)

0、0.06、0.1、0.2、0.3、0.5、0.8、1、4、10(s) note 4

Rated residual non-action current I△no

50%I△n

50%I△n

performance characteristics

simple sinusoidal alternating current

simple sinusoidal alternating current and pulsating direct current

frequency

50Hz±5Hz

50Hz±5Hz

action error

-20% ~ -10%I△n

-20% ~ -10%I△n

output

output mode

one is the normal closing and the other is for the transformation

one is the normal closing or opening, and the other is for the transformation

contact capacity

5A 250VAC  5A 30VDC

AL1:8A 250VAC  5A 30VDC

AL2:6A 250VAC  5A 30VDC

reset mode

the on-the-spot one and the long-distance one,

the on-the-spot one, the long-distance one and the automatic one

power supply

voltage range

AC110V、AC220V(permissible error±10%)

AC110V、AC220V、DC85-270V

(permissible error±10%)

power dissipation

≤5W

power frequency withstand voltage

The effective value of alternating current between the power supply, input and output: 2kV/1min

 

under the normal operation

temperature

operating temperature: -20℃ ~ +55℃

storage temperature: -30℃ ~ +70℃

 

 

 

humidity

≤95%RH, with moisture condensation, and corrosive gas place

height above sea level

≤2000m

class of pollution

Grade three

installation category

Type Ⅲ

 

 

Note 3:ASJ10L-LD1A rated residual action current I N is 10mA-30A continuously adjustable;

 

Note 4:ASJ10L-LD1A limit non-driving Time N is 0-10S continuously adjustable.

 

 

 

 

 

 

Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimension