ecuador Acrel AIM-T500 Industrial Insulation monitoring instrument

● Can monitor AC,DC or AC/DC under 690V mixed ungrounded system ● With fault warning and alarm function ● Connection monitoring of PE and IT systems. ● 1 channel RS485 ● 2 replay outputs ● Self-check function ● LCD display ● SOE event record

Product Description

 

 

Overview

     

 

       

    AIM-T500 insulation monitoring device is designed and developed by Acrel gathering the design experience of electric power meter industry for many years to monitor the insulation condition of low voltage IT distribution system (ungrounded system).

 

      The product adopts advanced micro controller technology, with high degree of integration, compact size and easy installation, and it integrates intelligence, digitalization and networking.

 

      The device, with many functions such as insulation fault warning, fault alarm, event recording and so on, can be used in the mines, glass factories, electric furnaces and test facilities, metallurgical plants, chemical plants, and exploded dangerous places, computer center, emergency power supply and other places to monitor the insulation status of IT system in real time. When insulation fault occurs, it will alarm and remind the staff to check the fault.

 

      The products conform to the requirements of enterprise standard Q/VDCL-26-2017 IT System Insulation Monitor.

 

 

 

 

 

Dispaly

 

 

 

 

 

 

 

Application

 

 

 

 

 

 

 

Features

 

 

1. Function of insulation resistance monitoring, warning and alarm for the monitored IT system.

 

2. Multiple fault indication function, such as relay alarm output and LED alarm output.

 

3. Advanced field bus communication technology, and it can communicate with the host computer management terminal and monitor the operation status of the IT system in real time.

 

4. Fault event recording function. It can record the time and type of failure to provide convenience for operators to analyze the operation status of the system and eliminate faults in time.

 

5. Applicable for insulation monitoring of AC, DC and AC / DC hybrid IT systems.

 

6. Self checking function. realize the fault self-inspection of instrument hardware circuit.

 

7. Broken line monitoring function. Monitor the connection condition of the PE/KE.

 

8. The free option of manual reset/automatic reset.

 

9. Wide range of measurement, Allowable leakage capacitance of the system is large.

 

 

 

 

 

Network

 

 

 

 

 

 

 

 

Technical Parameters

 

 

 

Item

Parameter

Accessory power supply

AC 85~265V; DC100~300V; 50/60Hz

Power dissipation

< 8W

System voltage

AC 0~690V; DC 0~800V; 40~460Hz

System application

IT system (online), Other system (offline)

Insulation monitoring

Measuring range

1k~10MΩ

 

Alarm range

10k~10MΩ

 

Resistance accuracy

1~10k,1k; 10k~10M, ±10%

 

system leakage capacitance

<500μF

 

Response time (Ce=1μF)

<5s

Internal parameters

Measuring voltage

<50V

 

Measuring current

<270μA

 

Internal DC impedance

≥180kΩ

Relay output

Error, Alarm, Warning

SOE

20 records (fault type, fault value, fault time)

Alarm type

LCD, LED indicator

Communication

RS485, Modbus-RTU

Impulse voltage / Pollution Level

8kV/Ⅲ

EMC/ Radiation

IEC61326-2-4

Environment

Working temperature

-10 ~+65℃

 

Storage temperature

-20~+70℃

 

Relative humidity

<95%, without condensation

 

Altitude

≤2500m

           

 

 

 

 

Dimension

 

 

 

 

 

 

 

 