PRODUCTS CENTER
new Zealand Acrel AKH-0.66/K K-30*20 Series of 100A/5A Split Core Current Transformers for Energy Meters IOT Platform Energy Consumption Monitoring
Category:
Product Description
Overview
AKH-0.66/K series split current transformers are mainly used in reconstructing projects of urban and rural power grids.
They can be mounted easily without removal of primary bus. They also can be operated with electricity, which prevents the normal utilization of electricity.
Thus, they save the manpower, material resources and financial resources and improve the efficiency of users. This series match with relay protection, measuring and metering equipment.
Coding Rule

Dispaly

Function

● Model: AKH-0.66/K K-30×20, 60×40, 80×40, 80×50, 80×80, 120×80, 120×60, 100×40, 130×40, 140×60, 160×80, 200×80
● Rated secondary current: 1A or 5A
● Rated primary current: 20-5000A
● Rated frequency: 50/60Hz
● Continuous overload: 120%In


● Protection level: IP30
● Operating temperature:-25℃-+50℃
● Storage temperature:-40℃-+80℃
● Relative humidity, no condensation:90%
● Standard&Certificate: CE; IEC; UL
Models
|
Size
Specification |
Outline size |
Through size |
Note |
||||
|
W |
H |
D |
a |
e |
Specification(A) |
Quality(kg) |
|
|
K-30×20 |
90 |
114 |
40 |
22 |
32 |
20-400 |
0.8-0.9 |
|
K-60×40 |
114 |
140 |
36 |
42 |
62 |
250-2000 |
1.0-2.0 |
|
K-80×40 |
122 |
162 |
40 |
42 |
82 |
300-3000 |
1.2-2.4 |
|
K-80×50 |
114 |
159 |
36 |
52 |
82 |
250-1000 |
1.1-1.4 |
|
K-80×80 |
144 |
159 |
36 |
82 |
82 |
250-1000 |
1.3-1.5 |
|
K-120×80 |
144 |
199 |
36 |
82 |
122 |
500-1500 |
1.5-2.3 |
|
K-120×60 |
164 |
214 |
52 |
62 |
122 |
400-5000 |
1.6-3.0 |
|
K-100×40 |
144 |
194 |
52 |
42 |
102 |
1000-5000 |
1.6-3.2 |
|
K-130×40 |
144 |
224 |
52 |
42 |
132 |
1000-5000 |
1.6-3.6 |
|
K-140×60 |
164 |
234 |
52 |
62 |
142 |
1000-5000 |
1.7-3.7 |
|
K-160×80 |
184 |
254 |
52 |
82 |
162 |
1000-5000 |
2.8-3.7 |
|
K-200×80 |
184 |
294 |
52 |
82 |
202 |
1000-5000 |
3.5-4.5 |

|
Type |
Rated current ratio(A) |
Precision degree |
Rated load,VA |
|
K-30×20 |
20-75/1A |
1.0
|
0.2 |
|
100-150/5(1)A |
1.0 |
||
|
200/5(1)A |
1.5 |
||
|
250-300/5(1)A |
0.5 |
1.5 |
|
|
350-400/5(1)A |
2.5 |
||
|
K-60×40 |
250-300/5(1)A |
1 |
1.5 |
|
350-450/5(1)A |
0.5 |
1.5 |
|
|
500-800/5(1)A |
2.5 |
||
|
1000-1250/5(1)A |
5 |
||
|
1500-2000/5(1)A |
10 |
||
|
K-80×40 |
300-450/5(1)A |
0.5 |
2.5 |
|
500-800/5(1)A |
5.0 |
||
|
1000-2000/5(1)A |
10 |
||
|
2500-3000/5(1)A |
0.2 |
10 |
|
|
K-80×50 |
250-300/5(1)A |
1 |
1.5 |
|
400-450/5(1)A |
0.5 |
1.5 |
|
|
500-800/5(1)A |
2.5 |
||
|
1000/5(1)A |
5 |
||
|
K-80×80 |
250-300/5(1)A |
1 |
1.5 |
|
400-450/5(1)A |
0.5 |
1.5 |
|
|
500-800/5(1)A |
2.5 |
||
|
1000/5(1)A |
5 |
||
|
K-100×40 |
1000-2000/5(1)A |
0.5 |
10 |
|
2500-3000/5(1)A |
0.2 |
10 |
|
|
4000-5000A/5(1)A |
15 |
||
|
K-120×60
|
400-450/5(1)A |
0.5 |
2.5 |
|
500-800/5(1)A |
5.0 |
||
|
1000-2000/5(1)A |
10 |
||
|
2500-5000/5(1)A |
0.2 |
10 |
|
|
K-120×80 |
500-800/5(1)A |
0.5 |
2.5 |
|
1000-1200/5(1)A |
5 |
||
|
1250-1500/5(1)A |
7.5 |
||
|
K-130×40 |
1000-2000/5(1)A |
0.5 |
10 |
|
2500-5000/5(1)A |
0.2 |
10 |
|
|
5000/5(1)A |
0.2 |
15 |
|
|
K-140×60 |
1000-2000/5(1)A |
0.5 |
10 |
|
2500-3000/5(1)A |
0.2 |
10 |
|
|
4000-5000/5(1)A |
15 |
||
|
K-160×80 |
1000-2000/5(1)A |
0.5 |
10 |
|
2500-3000/5(1)A |
0.2 |
10 |
|
|
4000-5000/5(1)A |
15 |
||
|
K-200×80 |
1000-2000/5(1)A |
0.5 |
10 |
|
2500-3000/5(1)A |
0.2 |
10 |
|
|
4000-5000/5(1)A |
15 |
Network

Details show
Installation