PRODUCTS CENTER


vatican Acrel ANet-1E1SM CE Approved Ethernet Modbus-TCP/IP Smart Gateway For EMS & IOT Platform Energy Consumption Monitoring

● Upstream Methods: Ethernet ● Upstream Protocol: Modbus-TCP/IP ● Downstream Methods: RS485 Interface ● Downstream Protocol: MODBUS-RTU ● Support: Up to about 25 Acrel Devices with RS485 (MODBUS-RTU) ● Power Supply: 24Vdc (default); 85~265Vac/Vdc (via AWT100-POW Module) ● Standard&Certificate: CE-RED; IEC; LVD; EMC

Product Description

 

 

Overview

     

        

 This series of intelligent communication management machine is a computer platform with embedded hardware, with multiple downlink communication interfaces and one or more uplink network interfaces. It is used to collect and summarize communication data of all intelligent monitoring/protection devices in a target area, upload it to the master station system in real time, and complete energy data acquisition functions such as remote communication and telemetry.

 

 Meanwhile, this series of intelligent communication management machine supports to receive the command issued by the superior master station system, and send it to the intelligent series unit in the target area, to complete the on/off remote control of the switch equipment in the station or device parameter setting, to achieve remote control and remote adjustment function, to realize the remote output dispatching command target.

 

 This series of intelligent communication management machine provides rich protocol library to support/realize the interconnection of intelligent devices from different secondary equipment suppliers. As a communication interface device between automation system network and monitoring equipment, this series of intelligent communication management machine has realized three functions: protocol conversion, interface matching and data conversion.

 

   This series intelligent communication manager provides an RS485 communication port. Each port supports a maximum of 32 instrumentation devices (for low-voltage comprehensive protection, users are advised to connect no more than four devices to each port). The number of devices carried by each communication port can be determined according to the communication baud rate, communication line length and customer's requirement for the refresh speed of communication data.

 

 This series of intelligent communication management machine real-time parallel multitasking processing and access to the third party equipment and the upper system connection communication, support software configuration. Special configuration management software enables you to select different communication protocols for devices mounted on different channels, and you can change the number and data information of instruments connected to the communication manager by changing the configuration file without changing the software program.

 

 

 

 

 

 

Coding Rule

 

       

       

      The specific model is located on the product label on the device side. The current list of models involved is as follows: 4 Serial port Series: ANet-2E4S1 (Iron case) 8 Serial port Series: ANet-2E8S1 (Iron case) 2 Serial port series: ANet-1E2S1, Anet-1E2S1-4G, ANet-1E1S1, Anet-1e1S1-4G (iron case) Modular   series:  ANet-2E4SM,  Anet-2E4SM-LR,  ANet-M4G,  ANet-M485   (plastic   case),   ANet-MCAN, ANet-MIO, ANet-MSE, ANet-MBUS, ANet-MALIBUS

 

 

 

 

 

 

 

Dispaly

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

 

 

 

● Communication: RS485(Modbus-RTU) / Ethernet gateway (1 opto-isolated RS485(Modbus-RTU)+ 1 RJ45(Ethernet))

 

● 220V power adapter is standardly equipped

   Can link to IOT Cloud Platform, Energy Management Systems, etc.

Features

● Modularity and flexible expansion.

● 8-way passive dry contact switching value acquisition, which can collect switching value

information such as instrument, access control, water immersion, smoke and so on in real
time.

● One 4G all Netcom wireless module can be expanded to provide 4G upload and 4G wireless routing

functions.

● Three 485 serial port modules can be expanded, and each serial port module provides four

RS485 serial interfaces.

● It supports operation for more than 5 seconds after power failure, and supports power failure

alarm requirements of some protocols.

● All expansion modules can be purchased separately, which is more convenient for on-site

environment transformation and business expansion and saves costs.
 

 

              

Network/Application

 

 

 

RS485 to Ethernet/4G/WiFi Solution Structure

 

 

 

 

 

 

 

 

 

 

 

 

 

Modular Series

 

 

 

 

 

 

 

 

 

Dimension

 

 

 

 

 

 

 

Installation

 

 

Notes:

1: Main module ANet-2E4SM

 

2. 3. 4: RS485 module ANet-M485

 

5: 4G wireless communication module ANet-M4G-HW

 

6: Network cable

 

7: 4G antenna

 

Main module 1, expandable RS485 modules 2, 3 and 4, 4G wireless communication module 5 and antenna 7. Main module 1 is physically connected with expandable RS485 modules 2, 3 and 4 and 4G wireless communication module 5 through network cable 6.

 

 

 

 

9: Press RST key, press it for 2-5 seconds to restart the equipment, and press it for more than 5 seconds to restore the factory default setting. 11: 8-way passive Di switching value interface.

 

10. Lora communication

 

11: 8-way passive Di switching value interface.
 

12: 4G wireless communication module ANet-M4G-HW expansion interface.

 

13. 14. 15: ANet-M485 expansion interface of RS485 module, 13 corresponds to serial port COM5-8, 14 corresponds to serial port COM9-12, and 15 corresponds to serial port COM13-16.

 

 

 

 

16: 2-way 10 / 100M network interface. The default factory IP address is lan1:
192.168.1.136; LAN2:192.168.2.136.
 
17: TF card interface, which can support max.32g TF card, hot plug and plug and play breakpoint continuous data storage.
 
18:USB2. 0 high-speed interface, supporting access to USB flash disk for breakpointcontinuous transmission.
 
19: 4-way RS485 communication.
 
20: Input voltage DC 9 ~ 36 V (standard power adapter: AC220V to DC12V).