Products

Acrel ATE300M Wireless Temperature Sensor for Cable/Busbar Temperature Monitoring

● Wireless frequency: 433-510 Mhz ● Communication distance: 1000m in open area ● Sampling frequency: 1-240s ● Range of temperature: -40℃~150℃ ● Accuracy: ±1℃ ● Power source: AC 85~265V、DC 100~300V ● Application: Joints in medium and low voltage panels ● Sensor probe: Options 1-6, split-type NTC: aperture 12mm, lengths 0.5m, 1.2m, 2.5m. ● Installation: Rail type/Tie type
Make an inquiry >
  • Product Description
  • Parameters
  • Q&A
  • Download
  •  

     

    Overview

         

     

     

            ATE series wireless temperature measuring sensor has been developed in compliance with Specification for Wireless Temperature Measuring equipment, NB/T 42086-2016. It is suitable for 3-35kV indoor switchgears, including built-in switchgears, handcart switchgears, fixed switchgears and loop-net switchgears. It is also suitable for 0.4kV low-voltage switchgears such as fixed switchgears and drawer switchgears. The wireless temperature sensors can be installed at any heating point in switchgears, the device utilizes the wireless data transmission technology for real-time transmission of monitored temperature data. In addition, it can be transmitted to display device or remote intelligent monitoring system.

     

     

     

     

    Coding Rule

     

     

     

     

     

     

     

    Dispaly

     

     

     

     

     

     

     

    ATE300M multi circuit temperature sensor is applicable to various occasions such as electrical connectors in low-voltage cabinet.

     

     

     

     

     

     

    Application

     

     

    1. Cable connector temperature measurement;  2. Contact temperature measurement;  3. Busbar temperature measurement

     

     

     

     

     

     

     

     

           

    Network

     

     

    Solution 1: Wireless temperature measurement of electrical contacts in high and low voltage cabinets

     

     

     

     

    Solution 2: Wireless temperature measurement of electrical contacts in high and low voltage cabinets

     

     

     

     

     

    Solution 3: On-site wall-mounted centralized display solution

     

     

     

     

    Solution 4: Upload data to IOT Platform

     

     

     

    Solution 5: Upload data to IOT Platform

     

     

     

    Dimension

     

     

     

     

    Installation

     

     

      Fix the sensor body in a suitable position inside the cabinet by binding it with guide rails or straps;

      The NTC probe is fixed by means of screws, bundling, or silicone bonding. Power the sensor with an AC 85~265V、DC 100~300V power supply, and the power indicator light flashes red twice when powered on.

     

     

     

     

    FAQ

     

    1. Is there any signal interference if more than 40 ACREL units are installed? 

    Reply: No.

     

    2. How to determine the ID of each sensor which is more than 40 units? 

    Reply: Every sensor sends the temperature data and its ID to ATC600, then transmits to ATP display screen and IOT platform.

    ATP dispaly screen and IOT platform can display the data and position of every sensor. The user can identify them easily.

     

    3. How to make sure the battery can last up to 5 years? 

    Reply: 5 years is the theoretical value calculated by the average current of the sensor. In actual use, it will be affected by various external factors, for example, the battery life will be greatly shortened under the condition of high temperature for a long time. 

     

    4. If the battery runs out in less than 1 year, what is the solution? 如果电池在1年内损坏或者电量耗尽,该怎么处理?

    Reply: There are 2 solutions:

    1. The batteries in the ATE and AHE sensors can be replaced by new ones.

    For ATE100M/200/200P, the Battery model is ER2450T.

    You have to welding the two points in the sensor when you change their batteries.

    For ATE400, it is strap mounted type, powered through electro-magnetic induction, it has no battery.

    For AHE100, its battery model is CR2450, the sensor has battery holder, so the battery is easier to be replaced.

    2. We can send new sensors to replace those ones with quality problems.

     

    5. Ensure the receiver's ability to read how many sensor units? 

    Reply: One ATC600-C can read the data of 240 sensors at most.

    One ARTM-Pn can read the data of 60 sensors at most.

     

    6. The current condition is that there are 4 receivers that will be installed, to ensure communication between receivers is not disrupted, for example: receiver 1 must read sensors in building 1, but sensors in building 2 are also read? 

    Reply: Every transceiver will only display the data of the sensors with the corresponding group number, and even if it receives data from other groups of sensors, it does not matter because each sensor has a unique ID and does not cause confusion. 

     

    7. What spare parts are available for the spare sensor unit? 

    Reply: Transceiver has antenna, connection terminals, ATE400 comes with alloy plate, non-slip pad, locking piece and screws. 

     

    8. How to distinguish AHE100 and ATE100M/ATE200 type sensor ID? is it enough with 1 receiver? 

    Reply: The answer is the same with that of the 2nd question.

    Yes, it is enough with 1 receiver.

     

    9. Do i have to send commands to the sensor for getting its temperature readings or it keeps sending temperature data automatically when connected?

    Reply: ATE400 sensor monitor the data and uploaded it to ATC600 and IOT every 15 S.

    ATE400 monitor tenperature and transmits the data every 15 s, it has nothing to do with temperature fluctuationi.

    ATE100/200 and AHE100 measure the temperature every 25S. If the temperature changes more than 4 degrees from the previous temperature, the data will be uploaded to ATC600 and IOT. If the temperature changes less than 4 degrees, the temperature will be uploaded every 5 minutes.

    if the temperature fluctuation is less than 4 ℃, is transmits every 5 minutes; if it is large than 4 ℃, it transmits every 25 s.

     

    10. How I should interpret the data when I connect the ATC600 directly to the PC (though RS485)? For example, how I identify each sensor with their respective temp?

    Register addresses and sensor codes correspond sequentially, one to one

     

    Other Question? Please contact us and we will get back to you as soon as possible.

     

    Product Description:
    • PView
    • high-performance
    • requirements
  • Technical Features

    项目

    Items

    指标

    Features

    环境要求

    Environment

    工作温度

    Temperature

    -40℃~85℃

    相对湿度

    Humidity

    ≤95%

    大气压力

    atmospheric pressure

    86kPa~106kPa

    ATE100M/100/200有源无线温度传感器

    ATE100M/100/200 Active wireless temperature sensor

     

    无线频率

    Wireless frequency

    470MHz、433Mhz

    通讯距离

    Communication distance

    空旷150m(470Mhz)、空旷50m(433Mhz)

    150m(470Mhz) 、50m(433Mhz)in open area

    采样频率

    Sampling frequency

    25s

    发射频率

    Transmitting frequency

    25s-5min

    工作电源

    Power source

    电池

    Battery

    安装方式

    Installation

    磁吸式/螺栓式/表带式

    Magnetic / bolted /Belt

    测温范围

    Range of temperature

    -50℃~+125℃

    精度

    Precision

    ±1℃

    应用范围

    Application

    高低压柜内电气接头

    Joints in high or low voltage switchgears

    电池寿命

    Battery life

    ≥5年(25℃)

    ≥5 years(25℃)

    400无源无线温度传感器

    400 Passive wireless temperature sensor

    无线频率

    Wireless frequency

    470MHz、433Mhz

    通讯距离

    Communication distance

    空旷150m(470Mhz)、空旷50m(433Mhz)

    150m(470Mhz) 、50m(433Mhz)in open area

    采样频率

    Sampling frequency

    15s

    发射频率

    Transmission frequency

    15s

    工作电源

    Power source

    CT感应取电,启动电流≥5A

    CT-powered, starting current≥5A

    最大工作电流(Max current)≤5000A

    安装方式

    Installation

    合金片固定

    alloy chip fixing

    传感器探头

    Sensor probe

    合金底座

    alloy bottom

    测温范围

    Range of temperature

    -50℃~125℃

    精度

    Precision

    ±1℃

    应用范围

    Application

    高低压柜内电气接头

    Joints in high or low voltage switchgears

    ATE100P/200P户外无线温度传感器

    ATE100P/200P Outdoor wireless temperature sensor

     

    无线频率

    Wireless frequency

    470MHz、433Mhz

    通讯距离

    Communication distance

    空旷150m(470Mhz)、空旷50m(433Mhz)

    150m(470Mhz) 、50m(433Mhz)in open area

    采样频率

    Sampling frequency

    25s

    发射频率

    Transmitting frequency

    25s-5min

    工作电源

    Power source

    电池

    Battery

    安装方式

    Installation

    螺栓式/表带式

     bolted /Belt

    测温范围

    Range of temperature

    -50℃~+150℃

    精度

    Precision

    ±0.5℃

    应用范围

    Application

    电气接头

    Voltage switchgears

    电池寿命

    Battery life

    ≥5年(25℃)

    ≥5 years(25℃)

    防护等级

    Protection level

    IP68

     

     

     

     

    ATE300M多回路式温度传感器

    ATE300M multi

    Loop temperature sensor

     

     

    无线频率

    Wireless frequency

    433-510MHz

    通讯距离

    Communication distance

    空旷1000m

    1000m in open area

    采集频率

    Sampling frequency

    1-240s

    工作电源

    Power source

    AC/DC 85~265V

    安装方式

    Installation

    导轨式/扎带式

    测温范围

    Range of temperature

    -40℃~+140℃

    精度

    Precision

    ±1℃

    应用范围

    Application

    低压抽屉柜内电气接头

    Joints in  low voltage switchgears

     

  •  

    1. Is there any signal interference if more than 40 ACREL units are installed? 

    Reply: No.

     

    2. How to determine the ID of each sensor which is more than 40 units? 

    Reply: Every sensor sends the temperature data and its ID to ATC600, then transmits to ATP display screen and IOT platform.

    ATP dispaly screen and IOT platform can display the data and position of every sensor. The user can identify them easily.

     

    3. How to make sure the battery can last up to 5 years? 

    Reply: 5 years is the theoretical value calculated by the average current of the sensor. In actual use, it will be affected by various external factors, for example, the battery life will be greatly shortened under the condition of high temperature for a long time. 

     

    4. If the battery runs out in less than 1 year, what is the solution? 如果电池在1年内损坏或者电量耗尽,该怎么处理?

    Reply: There are 2 solutions:

    1. The batteries in the ATE and AHE sensors can be replaced by new ones.

    For ATE100M/200/200P, the Battery model is ER2450T.

    You have to welding the two points in the sensor when you change their batteries.

    For ATE400, it is strap mounted type, powered through electro-magnetic induction, it has no battery.

    For AHE100, its battery model is CR2450, the sensor has battery holder, so the battery is easier to be replaced.

    2. We can send new sensors to replace those ones with quality problems.

     

    5. Ensure the receiver's ability to read how many sensor units? 

    Reply: One ATC600-C can read the data of 240 sensors at most.

    One ARTM-Pn can read the data of 60 sensors at most.

     

    6. The current condition is that there are 4 receivers that will be installed, to ensure communication between receivers is not disrupted, for example: receiver 1 must read sensors in building 1, but sensors in building 2 are also read? 

    Reply: Every transceiver will only display the data of the sensors with the corresponding group number, and even if it receives data from other groups of sensors, it does not matter because each sensor has a unique ID and does not cause confusion. 

     

    7. What spare parts are available for the spare sensor unit? 

    Reply: Transceiver has antenna, connection terminals, ATE400 comes with alloy plate, non-slip pad, locking piece and screws. 

     

    8. How to distinguish AHE100 and ATE100M/ATE200 type sensor ID? is it enough with 1 receiver? 

    Reply: The answer is the same with that of the 2nd question.

    Yes, it is enough with 1 receiver.

     

    9. Do i have to send commands to the sensor for getting its temperature readings or it keeps sending temperature data automatically when connected?

    Reply: ATE400 sensor monitor the data and uploaded it to ATC600 and IOT every 15 S.

    ATE400 monitor tenperature and transmits the data every 15 s, it has nothing to do with temperature fluctuationi.

    ATE100/200 and AHE100 measure the temperature every 25S. If the temperature changes more than 4 degrees from the previous temperature, the data will be uploaded to ATC600 and IOT. If the temperature changes less than 4 degrees, the temperature will be uploaded every 5 minutes.

    if the temperature fluctuation is less than 4 ℃, is transmits every 5 minutes; if it is large than 4 ℃, it transmits every 25 s.

     

    10. How I should interpret the data when I connect the ATC600 directly to the PC (though RS485)? For example, how I identify each sensor with their respective temp?

    Register addresses and sensor codes correspond sequentially, one to one

     

    Other Question? Please contact us and we will get back to you as soon as possible.

     