ARD2F CE Approved Smart Motor Protectors for Protecting Motors and Power Monitoring
Series of products: Products
Series of products: Power Monitoring and Controlling Devices
Series of products: Smart Motor Protectors
- Product Description
- Parameters
- Q&A
- Download
-
Overview
The ARD2F intelligent motor protector (hereinafter referred to as the protector) is suitable for low-voltage motor circuits with rated voltage up to 660V and integrates protection, measurement, control, communication, operation and maintenance.
Its perfect protection function ensures the safe operation of the motor, with logic programmable function, can meet a variety of control methods. The product adopts split structure, which is composed of main body, panel, mutual inductor and optional communication module, and can adapt to the installation of various cabinets.
Product Implementation standards: ——GB 14048.4-2020 Low-voltage switchgear and control gear -- Part 4-1: Contactors and motor starters -- Electromechanical contactors and motor starters (including motor protectors); ——JB/T 10736-2007 Low voltage motor protector.
Coding Rule

Dispaly

Application

Function
The ARD2F functional configuration is shown in below table:
Type
Function
Functional configuration
Standard function
Optional function
Protection function
Fixed time overload
√
Inverse time overload
√
Starting timeout
√
Phase loss
√
Voltage unbalance
√
Current unbalance
√
Locked-Rotor
√
underload
√
External fault
√
Block
√
Temperature protection(PTC/NTC)
√
Residual current
grounding
√
leakage
√(leakage)
Phase sequence
√
Under voltage
√
Over voltage
√
Under power
√
Over power
√
tE Time protect
√
Overflow protection
√
Alarm of starting times
√
Running time alarm
√
Fault frequency alarm
√
Control mode
Protection mode
√
Direct start mode
√
Two-step mode
Two-speed mode
Y-△ start mode
Voltage loss restart
√
Communication
1 channel Modbus-RTU communication
√
2 channel Modbus-RTU communication
√
1 channel Profibus-DP communication
√
1 channel Modbus-RTU+1 channel Profibus-DP
√
Switching input
9 channel DI(programmable)
√
Relay output
2 channel DO(programmable)
√
5 channel DO(programmable)
√
Analog output
1 channel DC4-20mA
√
Event record
Start record, stop record, DI displacement record, restart record, (support communication transmission and U disk export)
√
Panel
Liquid crystal display (LCD)
Black and white dot matrix LCD display
√
Additional features of ARD2F are shown in Table:
Additional function
Code
Additional function
Code
Starting control (including K function)
Q
Leakage protection
L
Switching input
K
4-20mA analog output
M
Temperature protection
T
Anti - electric shock function
SU
Alarm (Programmable output)
J
SOE event record
SR
1 channel communication
Modbus_RTU
C
2 channels communication
2路Modbus_RTU
2C
Profibus_DP
CP
Modbus+Profibus
CCP
Voltage function (phase sequence, power, power factor)
U
tE time protection
tE
Energy metering
Ep
Network

Product Features
■ Support fundamental and full-wave power parameter measurement (U, I, P, Q, S, PF, F, EP, EQ), voltage and current imbalance degree, voltage and current positive sequence, negative sequence, zero sequence component, three-phase voltage phase Angle, residual current.
■ Protection functions include overload inverse time, overload definite time, grounding, starting timeout, leakage, underload, locked-rotor, obstruction, short circuit, phase, overflow, imbalance (current, voltage, power, less power, overvoltage, undervoltage, phase sequence, temperature, external fault, tE time, running time alarm, fault alarm.
■ 9 channels programmable DI input, the default use of DC24V power supply, or external active wet contact can be selected (see the selection table).
■ 5 programmable DO output, to meet the direct starting, star - triangle starting, auto-transformer starting, and other starting modes, can be through the communication bus to achieve the master station to the motor remote control "start/stop".
■ Optional anti-shaking function: support immediate restart of shaking power and restart of voltage loss.
■ MODBUS_RTU and PROFIBUS DPV1 communication modules are available for selection.2 MODBUS_RTU communication channels or MODBUS-RTU+PROFIBUS DPV1 communication modules can be chosen.
■ Optional 1 channels DC4-20MA analog output interface, connected with DCS system, can realize the monitoring of field equipment.
■ With fault record, start record, stop record, DI displacement record, restart record and other records of various events, you can view a number of motor operation and maintenance information.
■ The display interface supports Chinese/English LIQUID crystal display
Dimension


Wiring

Package

Product Description:- PView
- high-performance
- requirements
-
Main parameters
The corresponding relation between ARD2F current specification and the rated current and power of the applicable motor is shown in Table 1:
Table 1
Protector current specification (A)
Ratio setting
Primary side coil number of transformer
Applicable scope of motor (kW)
Suitable for motor Rated current range (A)
1
Support
5circle
0.12-999
0.1-5000
5
1circle
0.12-999
0.5-5000
1.6
Does not support
1circle
0.12-0.55
0.4-1.6
6.3
1circle
0.75-2.2
1.6-6.3
25
1circle
3-11
6.3-25
100
1circle
15-45
25-100
250
1circle
55-132
63-250
800
1circle
160-250
250-800
Additional features of ARD2F are shown in Table 2:
Table 2
Additional function
Code
Additional function
Code
Starting control (including K function)
Q
Leakage protection
L
Switching input
K
4-20mA analog output
M
Temperature protection
T
Anti - electric shock function
SU
Alarm (Programmable output)
J
SOE event record
SR
1 channel communication
Modbus_RTU
C
2 channels communication
2路Modbus_RTU
2C
Profibus_DP
CP
Modbus+Profibus
CCP
Voltage function (phase sequence, power, power factor)
U
tE time protection
tE
Energy metering
Ep
See Table 3 for the ARD2F display module:
Table 3
Display module
code
90L
LCD display, module size 98×60, opening 92×55 (unit:mm)
Remarks:
(1).Current measuring and 2 channels of relay output DO4(97.98).DO5(94.96.95) are standard for ARD2F.
(2).When equipped with starting control, the protector provides no more than 2 starting relay for the sequence control of the closing/opening of two external contactors to realize different starting ways of motor (such as Y-Δ transformation starting, positive and negative rotation control, and self-coupling reduced-voltage starting, etc.)
(3).The additional function SU and Q should be chosen together. Additional function SU is including U(voltage function) and SR(SOE event record).
(4).The current specifications of 100A and below shall be the same type of current transformer. The transformer is equipped with a secondary line of about 1m. If you need special line length, please contact the manufacturer. The 250A and 800A current specifications use two other types of transformers with no secondary wires. See "External Dimensions and Installation" for the dimensions of the transformer.
(5).The standard display cable is a network cable with a length of 1.5m. 3 meters and 5 meters are available for optional configuration. You can place an order and remark the corresponding cable length.
(6).For customers who do not need display modules, a batch of optional several display modules can be used as a programmer, or the configuration software provided by the manufacturer can be used to configure parameters through computer software.
(7).The temperature measurement support sensor type is PTC or NTC.。
(8).After selecting the leakage function (L), each protector shall be equipped with a leakage transformer. Please refer to the "External Dimensions and Installation" section for the dimensions of the leakage transformer. The leakage transformer is equipped with a secondary wire of 2m±10cm. If other lengths are needed, please contact the manufacturer.
Technical indicators
ARD2F technical indicators are shown in Table 4:
Table 4
Technical parameters
Technical indicators
Protector auxiliary power supply
AC85-265V/DC100-350V
Rated working voltage of the motor
AC220V / 380V / 660V,50Hz / 60Hz
Rated operating current of the motor
1 (0.1A-5000A)
External current transformer
5 (0.1A-5000A)
1.6A(0.4A-1.6A)
6.3A(1.6A-6.3A)
25(6.3A-25A)
100(25A-100A)
250(63A-250A)
800(250A-800A)
Relay output contact capacity
Impedance load
AC250V.10A
Switching input
9 channels of passive dry contact (active DC110V, DC220V, AC220V input can be optional)
Communication
RS485 Modbus_RTU, Profobus_DP
Environment
Working temperature
-10ºC~55ºC
Storage temperature
-25ºC~70ºC
Relative humidity
≤95% No condensation, no corrosive gas
Altitude
≤2000m
Pollution levels
Class 3
Protection grade
Main body IP20, split display module IP54 (installed on the cabinet panel)
Installation category
Level III
Functional configuration
The ARD2F functional configuration is shown in Table 5
Table 5
Type
Function
Functional configuration
Standard function
Optional function
Protection function
Fixed time overload
√
Inverse time overload
√
Starting timeout
√
Phase loss
√
Voltage unbalance
√
Current unbalance
√
Locked-Rotor
√
underload
√
External fault
√
Block
√
Temperature protection(PTC/NTC)
√
Residual current
grounding
√
leakage
√(leakage)
Phase sequence
√
Under voltage
√
Over voltage
√
Under power
√
Over power
√
tE Time protect
√
Overflow protection
√
Alarm of starting times
√
Running time alarm
√
Fault frequency alarm
√
Control mode
Protection mode
√
Direct start mode
√
Two-step mode
Two-speed mode
Y-△ start mode
Voltage loss restart
√
Communication
1 channel Modbus-RTU communication
√
2 channel Modbus-RTU communication
√
1 channel Profibus-DP communication
√
1 channel Modbus-RTU+1 channel Profibus-DP
√
Switching input
9 channel DI(programmable)
√
Relay output
2 channel DO(programmable)
√
5 channel DO(programmable)
√
Analog output
1 channel DC4-20mA
√
Event record
Start record, stop record, DI displacement record, restart record, (support communication transmission and U disk export)
√
Panel
Liquid crystal display (LCD)
Black and white dot matrix LCD display
√
-
Related Products