AMC16Z-FAK48 Digital Multi Circuits Energy Meter For Data Center Energy Consumption Monitoring
Series of products: Products
Series of products: Energy Management
Series of products: Multi-channel Energy Meters
Series of products: Multi-channel AC Energy Meters
Series of products: Din Rail Installed Energy Meters
Series of products: Din Rail Installed AC Energy Meters
Series of products: Data Center/Tower Base Station/Battery Monitoring
Series of products: Multi-channel Energy Meters for Data Center
- Product Description
- Parameters
- Q&A
- Download
-
Overview
With the rapid development of data center, the energy consumption problem of data center is becoming more and more prominent. The energy management and power supply and distribution design of data center have become a hot issue.
Efficient and reliable power distribution system scheme of data center is an effective way to improve the power consumption efficiency of data center and reduce the energy consumption of equipment. In order to realize energy saving in data center, it is necessary to monitor each electrical load first. However, there are many load circuits in data center. Traditional measuring instruments cannot meet the requirements of cost, volume, installation, construction and other aspects. In this case, the multi-circuit monitoring device which is suitable for centralized monitoring in data center is necessary to be used.
AMC16Z series AC precision power distribution monitoring device is specially designed for data center server power management.The device designed exquisite, can provide A + B 2 incoming and 96 outgoing’s electrical parameters, the input and output switch and the state of lightning protection device with real-time monitoring.
All alarm threshold of measurement channels can be set in separate. Over-outgoing triggers system acoustooptic warning immediately. Highly integrated monitoring loop is realized in the volume of traditional instruments.
Dispaly

Application



Installation in Data Center
Network

Function

Dual AC Outgoing Circuits Monitoring
● A+B Dual-side independent AC Circuits Monitoring
● Full Electrical Parameters Monitoring
● Outgoing Branch Circuits Multi-metering
Multiple Branch Circuits Metering
● Both 1-phase&3-phase Metering
● Max 48 circuits 1-phase
● Max 16 circuits 3-phase
● Mixed 8 circuits 3-phase and 24 circuits 1-phase for example
● Measures 3 phase power, total power (active, reactive, apparent), U, I, P, Q, S, PF, F, zero sequence current, voltage/current phase angle, voltage/current degree of unbalance, etc.


Power Quality Analysis
● 2nd~31st Harmonic
● Total Harmonic
Wiring & Installation


Dimension
Product Description:- PView
- high-performance
- requirements
-
1. Function Overview
Function Description Measurement
(Common)
Three-phase AC kWh, kVarh, Active Power, Reactive Power, Current, Voltage, Power Factor, Apparant Power, Frequency, Zero ground voltage, neutral line current
Measurement
(Power Quality)
total harmonic content (THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest coefficient (CF),telephone waveform factor (THFF), peak voltage, voltage and current sequence quantity
Temp.&Humidity
Monitoring
Tempeatrue Monitoring Range: -40℃~+99℃
Humidity Monitoring Range: 20%~90%
Leakage Current
2-channel Leakage Current Measurement
Accuracy
Electrical Parameter Metering Accuracy: Voltage/current level 0.2, active power/electric energy level 0.5,reactive power/electric energy level 1
Temperature Metering Accuracy: ±1℃; Temperature Metering Accuracy: ±5%
Communication
RS485 Interface (MODBUS-RTU protocol)
DO
(Swtich Output)
2-channel DO (Digital Output); 3A 250VAC/3A 30VDC
DI
(Swtich Input)
6-channel DI (Digital Input); dry contact
2. Main Parameters
Parameter Description&Value Voltage
Input
Rated Voltage 3x220~264Vac L-N
Reference Frequency 45~65Hz Current
Input
Rated Current 3x1(6)A AC (via CTs) Power
Supply
Source from Voltage Input (Voltage signal input for both measurement and power supply) Installation
DIN-rail 35mm standard DIN-rail Installation Phase
Wiring
3P4W 3-phase 4-wire Safety
Insulation
All terminals and the insulation resistance between the conductive pieces not less than 100MΩ
Withstand voltage
A-way voltage and current signal, B-way voltage and current signal, switch output and other ports should meet AC2kV 1min in pairs, the switch input and other ports should meet ac0.5kv 1mim, leakage current should be less than 2mA, no breakdown or flashover
3. Environment
Condition Description&Value Temperature
Operating Temperature: -20℃~+55℃; Storage Temperature: -40°C ~+70°C
Humidity
≤95%RH,no condensation,without corrosive gas
Altitude
≤ 2000m