Acrel AMC200L-4E3/4G Digital Multi-Circuit AC Electricity Meter with 4G Communication For Tower Base Station Energy Consumption Monitoring

● Funtion:full power parameter measurement, Active 2DI + Passive 4DI + 2DO, 4 NTC Temperature, 1 T&H ● Circuit:4 or 8 Channels 3 phase or 12 or 24 channels single phase mA class current sensor ● RS485(Modbus RTU protocol), 4G ● Power supply: AC/DC 85-265V ● Applicaiton: telecom Base station,other multi channels applicaiton
Make an inquiry >
  • Product Description
  • Parameters
  • Q&A
  • Download
  •  

     

    Overview

         

            

                  AMC 200(L) AC multi-circuit intelligent power acquisition and monitoring device is mainly used for the full electric parameter measurement of multiple circuits, and can simultaneously access the current input of 8 three-phase circuits or 24 single-phase circuits at most.

     

        It can measure voltage, current, power, power factor and other parameters.

     

     

     

     

     

    Dispaly

     

     

     

     

     

     

     

    Application

     

     

     

     

    Installation in Tower Base Station

     

     

     

     

     

    Network

     

     

     

     

     

     

     

     

     

    Models

     

     

     

     

    Instrument model

    basic skills

     

    AMC 200 - 4 E 3

    Can be connected to 4 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement

    AMC200-4E3/4G

    Can be connected to 4 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , 4G communication

    AMC200-4E3/NB

    Can be connected to 4 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , NB communication

    AMC 200 - 8 E 3

    Can be connected to 8 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement

    AMC200-8E3/4G

    Can be connected to 8 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , 4G communication

    AMC200-8E3/NB

    Can be connected to 8 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , NB communication

    AMC 200L - 4 E 3

    Can be connected to 4 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , with LCD display

    AMC200L-4E3/4G

    Can be connected to 4 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , 4G communication, with LCD display

    AMC200L-4E3/NB

    Can be connected to 4 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , NB communication, with LCD display

    AMC 200L - 8 E 3

    Can be connected to 8 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , with LCD display

    AMC200L-8E3/4G

    Can be connected to 8 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , 4G communication, with LCD display

    AMC200L-8E3/NB

    Can be connected to 8 three-phase AC circuits at the same time, can directly measure parameters such as voltage, current, power, power factor, etc., 6-way switch input (2-way active, 4-way passive), 2-way switch value output, 1-way RS485, 4 channels of NTC temperature measurement, 1 channel of temperature and humidity measurement , NB communication, with LCD display

     

     

     

     

     

     

     

    Function

     

     

     

    The specific functions are as follows:

     

    1maximum 8 three-phase or 24 single-phase circuit full electric parameter measurement, current transformer external;

     

    2monitor the phase voltage/current, zero sequence current, frequency;

     

    3monitor the phase power, total power (active power, reactive power, apparent);

     

    4monitoring each phase power factor, total power factor, four-quadrant power statistics;

     

    5the use of simplified Chinese characters LCD display, English Version also. with historical power data and historical alarm information storage function:

     

    a. By default, historical data is saved once a day at 0 o 'clock. Each channel and each item of data (total active power, total active power, and three-phase current) can be stored 1000 times.

     

    b. The interval for storing historical data onsite is 15 minutes. Each channel and each item of data (total active energy, total active power, three-phase current)can be stored 5000 times.

     

    c. 24 pieces of historical electricity data are stored on the monthly meter reading day.

     

    d. Historical alarms are stored in real-time mode. A maximum of 500 historical alarms can be stored.

     

    6support over voltage, over current, phase break, DI linkage alarm output;

     

    7four passive switching input, two active switching input, two switching output;

     

    8standard RS485 communication, optional Modbus-RTU protocol or YD/T 1363 protocol;

     

    9one loop temperature and humidity measurement, 4 loops  NTC measurement;

     

     

     

     

           

    Technical Parameters

     

     

     

     

     

    Technical Parameters

    technical indicators

    enter

    frequency

    45~65Hz;

     

    Voltage

    Rated value: AC 3×220V/380V;

     

     

    Overload: 1.2 times rated value (continuous); 2 times rated value/1 second;

     

     

    Power consumption: ≤0.5VA (per channel);

     

    electric current

    Rated value: AC xxxA/50mA, external transformer is required;

     

     

    Overload: 1.2 times rated value (continuous); 10 times rated value/1 second;

     

     

    Power consumption: ≤0.5VA (per channel);

    Function

     

    Pulse output

    Output mode: open collector optocoupler pulse (default 400imp/ kW h );

     

    communication

    Modbus-RTU protocol or YD/T 1363 protocol ;

    Baud rate 1200~38400; optional 4G communication or NB communication;

     

    open

    close

    quantity

    enter

    4 dry contact inputs, 2 active wet contact inputs (AC 220V);

     

     

    output

    Output mode: relay normally open contact output;

    Contact capacity: AC 250V/3A or DC 30V/3A;

     

    NTC temperature measurement

    Temperature: -20~100°C (accuracy ±2°C);

     

    Temperature and humidity measurement

    Temperature: -20~100°C (accuracy ±2°C); Humidity: 20-90%RH (accuracy ±5%RH)

    measurement accuracy

    Frequency 0.05Hz, voltage and current level 0.5, active energy level 1;

    Auxiliary power

    AC/DC 85~265V; power consumption≤10VA;

    safety

    Power frequency withstand voltage

    >AC 2kV/1min;

     

    Insulation resistance

    Input and output terminals to shell>100MΩ;

    environment

    Working temperature: -20℃~+60℃;

    Storage temperature: -40℃~+70℃;

    Relative humidity: ≤95% without condensation;

    Altitude: ≤2500m;

    Electromagnetic Compatibility

    Surge (shock) immunity test level 4;

     

    Electrostatic discharge immunity test level 3

     

    Electrical fast transient burst immunity test level 4

     

     

     

     

     

     

     

    Matching Transformers

     

     

     

            The current transformer is a crystal head interface, the primary side current is 100A-600A, and the secondary side output current is 50mA. If the current transformer is different, the customer can modify the current transformation ratio through the instrument interface or communication according to the actual usage. Transformer shown in Figure 1

     

     

     

     

    model

    Ratio

    line length

    precision

    installation method

    AKH-0.66/W-12NY 100A/50mA

    100A/50mA

    (1+0.2)m

    Level 0.2

    Closed type, crystal head interface

    AKH-0.66/K-Φ16N 100A/50mA

    100A/50mA

    (1+0.2)m

    Level 0.5

    Open type, crystal head interface

    AKH-0.66/W-20Y 200A/50mA

    200A/50mA

    (1+0.5)m

    Level 0.2

    Closed type, crystal head interface

    AKH-0.66/K-Φ24N 200A/50mA

    200A/50mA

    (1+0.5)m

    Level 0.5

    Open type, crystal head interface

    AKH-0.66/W-30NY 250A/50mA

    250A/50mA

    (1+0.5)m

    Level 0.2

    Closed type, crystal head interface

    AKH-0.66/K-Φ24N 250A/50mA

    250A/50mA

    (1+0.5)m

    Level 0.5

    Open type, crystal head interface

    AKH-0.66-TD-Φ60-NY

    400A/50mA

    (1+0.5)m

    Level 0.2

    Closed type, crystal head interface

    AKH-0.66/K-Φ36N 400A/50mA

    400A/50mA

    (1+0.5)m

    Level 0.5

    Open type, crystal head interface

    AKH-0.66-TD-Φ60-NY

    600A/50mA

    (1+0.5)m

    Level 0.2

    Closed type, crystal head interface

    AKH-0.66/K-Φ36N 600A/50mA

    600A/50mA

    (1+0.5)m

    Level 0.5

    Open type, crystal head interface

     

     

     

     

     

     

     

    Wiring

     

     

     

     

     

     

     

     

    Dimension

     

     

     

     

     

     

    Product Description:
    • PView
    • high-performance
    • requirements
  •  

     

    Technical Parameters

     

     

    Technical Parameters

    technical indicators

    enter

    frequency

    45~65Hz;

     

    Voltage

    Rated value: AC 3×220V/380V;

     

     

    Overload: 1.2 times rated value (continuous); 2 times rated value/1 second;

     

     

    Power consumption: ≤0.5VA (per channel);

     

    electric current

    Rated value: AC xxxA/50mA, external transformer is required;

     

     

    Overload: 1.2 times rated value (continuous); 10 times rated value/1 second;

     

     

    Power consumption: ≤0.5VA (per channel);

    Function

     

    Pulse output

    Output mode: open collector optocoupler pulse (default 400imp/ kW h );

     

    communication

    Modbus-RTU protocol or YD/T 1363 protocol ;

    Baud rate 1200~38400; optional 4G communication or NB communication;

     

    open

    close

    quantity

    enter

    4 dry contact inputs, 2 active wet contact inputs (AC 220V);

     

     

    output

    Output mode: relay normally open contact output;

    Contact capacity: AC 250V/3A or DC 30V/3A;

     

    NTC temperature measurement

    Temperature: -20~100°C (accuracy ±2°C);

     

    Temperature and humidity measurement

    Temperature: -20~100°C (accuracy ±2°C); Humidity: 20-90%RH (accuracy ±5%RH)

    measurement accuracy

    Frequency 0.05Hz, voltage and current level 0.5, active energy level 1;

    Auxiliary power

    AC/DC 85~265V; power consumption≤10VA;

    safety

    Power frequency withstand voltage

    >AC 2kV/1min;

     

    Insulation resistance

    Input and output terminals to shell>100MΩ;

    environment

    Working temperature: -20℃~+60℃;

    Storage temperature: -40℃~+70℃;

    Relative humidity: ≤95% without condensation;

    Altitude: ≤2500m;

    Electromagnetic Compatibility

    Surge (shock) immunity test level 4;

     

    Electrostatic discharge immunity test level 3

     

    Electrical fast transient burst immunity test level 4